Not sure I can (legal reasons?), but suffice to say thay feed multiple stations with multiple relatively large machines (+10MW). In some cases they have daisy-chained basins, so there are also level inner-loops to be tuned. So the approach has been using the pidtuner for tuning the inner loops first by keeping the outloops in manual. Then tune the loops outwards using the same approach. This has been the winning combination.

discuss

order

rhodozelia|4 years ago

Thanks for the details. I have not worked on a plant that had intake gates upstream of a headpond so was curious as to what the layout was. The nice thing about hydro is that just about every plant is unique!