True, skin effect limits the conductor size (~22mm in Al @60Hz) but overhead transmission already uses bundled conductors to address that as well as to improve mechanical strength, cooling, and reactance. The advantage of HVDC is in the lower dielectric and reactive losses while skin effect is minimal.