bradfa | 1 month ago
But bus bars generally should be protected regardless of voltage as they carry currents from high current capacity sources so even a lower voltage can be a safety concern.
Many server power supplies can take AC or DC input, with the DC input in the 300-500V range as this is comparable to the boost voltage for the AC power factor correction circuit. I just assumed most data centers using DC would be distributing around 400V within each rack.