Oh wow, what a bad memory. This exact thing happened in a building I lived in several years ago, a couple of floors above me. It looked like waterfalls outside our windows and water was rushing in under the baseboards. All while every fire alarm in the building was going off and fire truck sirens were blaring outside. Understandably, the fire department would not turn off the water until they had been to every floor to check for fire. On the upside, it's impressive how much water can be delivered by fire sprinklers.

Closer to the topic, the building's management company tried to come after me (a renter) for the expense of the restoration people who were brought in to rip out my drywall and carpet so mold wouldn't form. Maybe they figured tenants were an easier target than the contractor's insurance? Oh, and the management company were the ones who selected and hired the contractors. I had to get very aggressive, with plenty of threats of legal action, to get them to back down. That was fairly easy to do as my state's laws specifically specify liability rules for flooding in multi-tenant buildings. They never did do repairs while I was there - I moved out when my lease expired nearly a year later as they were tying to raise the rent, with drywall still missing.

discuss

order

quickthrowman|22 days ago

Oh man, multi-tenant housing sounds like the worst case scenario for this sort of thing. I’m glad you were able to avoid any liability, trying to pin liability for rebuilding a unit on a tenant is insane.

And yeah, the volume of water a fire pump can move is astounding. Electrical code requires the fire pump to be wired so that it can run at its locked rotor amp rating without tripping overcurrent protection and it’s usually tapped directly off the utility transformer separately from the rest of the electrical service. There’s also a smaller jockey pump that maintains water pressure in the system so that when the main pump turns on, there’s no lag with water coming out. The pump motor will keep spinning even if there’s a dead short if it’s fused right above locked rotor amps, since replacing a motor is cheaper than replacing a fully burned out structure and keeping the water flowing allows as many people to escape as possible. The feeder has to be encased in concrete or it has to be fire-resistant cable.